Are you in need of part numbers A85A0005-199, TFK236125WL from General Electric Inc manufacturers of NSN 5925010229731? ASAP Parts Online has the part number in stock and ready to be shipped. Along with NSN 5925010229731 corresponding part numbers, we have access to billions of premium parts such as Circuit Breaker for the aviation, defense, and military industries. We are here to help streamline the process.
Alternative NSN: 5925-01-022-9731 |
Item Name:Circuit Breaker |
FSG: 59 Electrical and Electronic Equipment Components |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NIIN: 010229731 |
NCB Code: USA (01) |
Manufacturers: General Electric Inc |
Part No Part No
|
Item Name Item Name
|
Manufacturer Manufacturer
|
QTY QTY
|
RFQ RFQ
|
---|---|---|---|---|
A85A0005-199 | circuit breaker | General Electric Inc | Avl |
|
TFK236125WL | circuit breaker | General Electric Inc | Avl |
|
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 10 125 INCHES NOMINAL |
ADAT | BODY WIDTH | 4 125 INCHES NOMINAL |
ADAU | BODY HEIGHT | 3 188 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 7 750 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1 375 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0 188 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 7 750 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1 375 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0 219 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 125 0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600 0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 22000 0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125 0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4 000 MINIMUM AT 100 PCT AND 11 000 MAXIMUM AT 100 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40 0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60 0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
Guaranteed quotes back within
5 minutes, 24/7 x 365
All Orders are fulfilled in the USA.
All shipments must comply with U.S.A export laws.
No exceptions.
The only independent distributor
with a NO CHINA SOURCING Pledge
Don't Forget That We Can Give You a Quote for Parts Within 15 Minutes If You Fill Out The Instant RFQ Form On Our Page.
Request for Quote