Are you in need of part numbers CD3-C3-A-50-240-3 from Eaton Corporation manufacturers of NSN 5925013179323? ASAP Parts Online has the part number in stock and ready to be shipped. Along with NSN 5925013179323 corresponding part numbers, we have access to billions of premium parts such as Circuit Breaker for the aviation, defense, and military industries. We are here to help streamline the process.
Alternative NSN: 5925-01-317-9323 |
Item Name:Circuit Breaker |
FSG: 59 Electrical and Electronic Equipment Components |
Federal Supply Class (FSC): 5925 Circuit Breakers |
NIIN: 013179323 |
NCB Code: USA (01) |
Manufacturers: Eaton Corporation |
Part No Part No
|
Item Name Item Name
|
Manufacturer Manufacturer
|
QTY QTY
|
RFQ RFQ
|
---|---|---|---|---|
CD3-C3-A-50-240-3 | circuit breaker | Eaton Corporation | Avl |
|
MRC | Criteria | Characteristic |
---|---|---|
ADAQ | BODY LENGTH | 5 790 INCHES MINIMUM AND 5 810 INCHES MAXIMUM |
ADAT | BODY WIDTH | 3 108 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2 740 INCHES MINIMUM AND 2 760 INCHES MAXIMUM |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0 209 INCHES MINIMUM AND 0 229 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3 537 INCHES MINIMUM AND 3 557 INCHES MAXIMUM |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50 0 AMPERES AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150 0 ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0 280 MINIMUM AT 200 PCT AND 1 000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS RESISTANT |
FREQ | FREQUENCY IN HERTZ | 400 0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1 016 INCHES MINIMUM AND 1 036 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2 599 INCHES MINIMUM AND 2 619 INCHES MAXIMUM |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE TWO AND THREE LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQJX | NOMINAL THREAD SIZE | 0 138 INCHES |
THSD | THREAD SERIES DESIGNATOR | UNC |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1 016 INCHES MINIMUM AND 1 036 INCHES MAXIMUM |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240 0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000 0 AC ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
Guaranteed quotes back within
5 minutes, 24/7 x 365
All Orders are fulfilled in the USA.
All shipments must comply with U.S.A export laws.
No exceptions.
The only independent distributor
with a NO CHINA SOURCING Pledge
Don't Forget That We Can Give You a Quote for Parts Within 15 Minutes If You Fill Out The Instant RFQ Form On Our Page.
Request for Quote